JULY 2020
Sampling Point | Date and Time of Sampling |
Heterotrophic Plate Count (Est. CFU/mL) |
Total Coliform (MPN/100mL) |
Thermotolerant Coliform / E. coli (MPN/100mL) |
Remarks |
---|---|---|---|---|---|
Catimon | July 8, 2020 - 8:25 AM | <1 | <1.1 | <1.1 | PASSED |
Narvacan | July 8, 2020 - 5:53 AM | 1 | <1.1 | <1.1 | PASSED |
Casongsong | July 8, 2020 - 5:25 AM | 1 | <1.1 | <1.1 | PASSED |
San Marcelino | July 8, 2020 - 4:45 AM | <1 | <1.1 | <1.1 | PASSED |
Balbalino | July 8, 2020 - 4:35 AM | 1 | <1.1 | <1.1 | PASSED |
Villa Felipe | July 8, 2020 - 4:10 AM | 260 | <1.1 | <1.1 | PASSED |
Nagpandayan | July 8, 2020 - 8:18 AM | <1 | <1.1 | <1.1 | PASSED |
Banitan | July 8, 2020 - 8:02 AM | 9 | <1.1 | <1.1 | PASSED |
Balingog West | July 8, 2020 - 7:55 AM | 2 | <1.1 | <1.1 | PASSED |
Zulueta Subd. | July 8, 2020 - 7:34 AM | <1 | <1.1 | <1.1 | PASSED |
Cawayan Bugtong | July 8, 2020 - 7:29 AM | <1 | <1.1 | <1.1 | PASSED |
Naglabrahan | July 8, 2020 - 7:00 AM | 9 | <1.1 | <1.1 | PASSED |
San Miguel | July 8, 2020 - 6:03 AM | 3 | <1.1 | <1.1 | PASSED |
San Roque Pump Station | July 8, 2020 - 7:22 AM | <1 | <1.1 | <1.1 | PASSED |
Maturanoc Pump Station | July 8, 2020 - 6:35 AM | 20 | <1.1 | <1.1 | PASSED |
Escano | July 8, 2020 - 6:15 AM | 2 | <1.1 | <1.1 | PASSED |
Bantug Pump Station | July 8, 2020 - 7:50 AM | 2 | <1.1 | <1.1 | PASSED |
San Rafael Pump Station | July 8, 2020 - 5:50 AM | 1 | <1.1 | <1.1 | PASSED |
Bacayao Pump Station | July 8, 2020 - 5:15 AM | 1 | <1.1 | <1.1 | PASSED |
San Andres Pump Station | July 8, 2020 - 4:25 AM | 340 | <1.1 | <1.1 | PASSED |
Sta. Veronica Pump Station | July 8, 2020 - 4:00 AM | 430 | <1.1 | <1.1 | PASSED |
St. John | July 8, 2020 - 4:03 AM | 290 | <1.1 | <1.1 | PASSED |
PNSDW Limits AO 2017-0010 | <500 | <1.1 | <1.1 |
MPN/100mL Most Portable Number per 100 mililiters
Note:
1. Tested method used:
a.) Pour Plate Method for the determination of the Heterotrophic Plate Count
b.) Multiple Tube Fermentation Technique for the determination of Total and Fecal/Thermotolerant coliforms
a.) Philippine National Standards for Drinking Water, 2017
b.) Standard Methods for the Examination of Water and Wastewater, 22nd Edition, 2012, APHA, AWWA, WEF
3. Result of examination specifically relates to samples as received